New Air Terminal in Bari-Palese



CLIENT
Transport and Navigation Ministry
Apulia Region
Seap SpA

DESCRIPTION
New Air Terminal in Bari-Palese

WORKS

MACHANICAL PLANTS
Cold store facility 4 thermal MW;
TPS 2,1 thermal MW;

THERMAL – FLUID PLANT
Cooling and heating plants
Water facilities
Fire – fighting facilities
Air conditioning plants
Water health plants
Green area irrigation plants
Fire – fighting plants

ELECTRICAL AND SPECIAL PLANTS
Electrical substation and boards
E.M.F. production facility
Lighting plants
Electrical E.M.F plants
Electrical plants supplying technological ones

COM PLANTS
Auxiliary plants
Phone-data plants
Public address systems
TVCC plants
Access control plants
Intrusion plants
Flight Information Plants
Fire and gas detection plants
Supervision and control plants

MAIN EQUIPMENTS
U.T.A.(rate: 936 ÷ 49900 m³/h) no. 20
Ejectors (rate: 150÷ 8250 m³/h) no.22
Fume extraction ejectors (20,000 ÷ 30,000 m³/h) no. 7
Spiral heat exchanger 750kW no. 2
Electro pumps for water (720 ÷ 375,000 l/h) no. 38
• “Under/over” air conditioning plants of 7 ÷ 10 kW no. 6
Air blade barriers no. 12
Mixer boxes no. 115
Air muting no. 55
Fire line rolling shutter no. 175
Helicoid warm air grilles no. 650
Air discharge long-range nozzles no. 305
Ambient air shooting jets no. 250
Steel pipeline Kg 120.000 (~ 15 km)
Channels for air conditioning m² 30,000

FIRE – FIGHTING EQUIPMENTS
Above ground hydrant UNI 70 DN 100 no. 26
Wall hydrant UNI 45 no. 74
Water hydrant l. 6 – cl. 21A-233BC no. 60
Dry powder extinguisher 30kg – cl. A-B1-C no. 4
Dry powder ext. kg 6 with intern. jet cl. 34A 233 C no. 70
Dry powder extinguisher kg 6 – cl. 34A 233BC no. 18
CO2 extinguisher kg 5 – cl. 113 B-C no. 16
• “Pendent” Sprinkler – 68°C ø ½” no. 1,203
• “Pendent” Sprinkler – 93°C ø ½” no. 319
• “Up-Right” Sprinkler – 68°C ø ½” no. 418
Fire-fighting press. hydrants group no. 1
Fire-fighting press. Sprinkler group no. 1
Wet control DN 100 Sprinkler group no. 1
Pre action control DN 150 Sprinkler group no. 1

MAIN DATA

AIR CONDITIONIN PLANT FOR SUMMER AND WINTER

THERMAL NEEDS
Total thermal winter need 3,220 kW
Total summer refrigerated need 3,250 kW
Outdoor air heat recovery 390 kW

HOT WATER MANUFACTURERS
Boiler for heating 1,045 kW no. 2
Boilers for the production of domestic hot water 200 kW
no. 1
Heat pumps 530 kWf each. no. 2

TOTAL HEAT RATING 3,350 kW

REFRIGERATED WATER MANUFACTURERS
Air cooling refrigerated groups to cool the water 1.250 kWf no. 2
Heat pumps 745 kWf each. no. 2

TOTAL REFRIGERATED POWER 3,900 kWf

HEAT RATING RECOVERED DURING SUMMER BY THE REFRIGERATED GROUPS AND HEAT PUMPS
850÷1040 kWt

TOTAL FLUID RATES
Hot water 285 ÷ 375 m³/h
Refrigerated water 600 ÷ 750 m³/h
Air treated for cond. 400.000 m³

6detail of mechanical plants
7
detail of thermal – fluid plants
5
detail of electrical and special plants
4
detail of COM plants
3
detail of main equipments
2
detail of main equipments
1
detail of fire- fighting equipments

FOTOGALLERY

 

 

Site Map |

Privacy |

Credits

 
© 2009 Guastamacchia spa Via P.Ravanas, 2 - 70037 Ruvo di Puglia (Ba) Tel +39.080.3601419 | info@guastamacchiaspa.com | P.IVA 03182110720